about.htm lintern_quality.htm products.htm Compressors.htm what's_new.htm Sales Reps.htm Load Questionnaire.htm
| |
New 3000 Series Condenser
The Lintern line-up of extreme-duty condenser units have been engineered
to utilize environmentally acceptable refrigerants and compatible lubricants.
The new 3000 series condensers are suitable for split type
applications. Their versatile design allows for application on cranes,
control rooms, operating pulpits, and other enclosures to cool and protect
personnel and equipment when married with the appropriate evaporator(s) section.
The 3000 series is built around a modular design which
enables us to add coils and tailor a compressor to create a system specifically
for your unique application. These condensers are designed to deliver 1-1/2 to 5
tons (5.3kW to 17.6kW) of cooling.
Designed for applications where ambient operating temperatures range
from 80°F (26°C) to 160°F (71°C), and where equipment is exposed to dirty and
corrosive environments or high vibration.
(Model Shown: 336 Condenser Semi)
(Model Shown: 348 Condenser Semi)
The 3000 series offers these unique features and benefits:
-
Heavy-Duty Frame Construction: 11-Gauge steel frame
painted epoxy. All welded frame for greater durability and corrosion
resistance in industrial environments. Modular design, units can be
mounted side-by-side or stacked on top of each other. Stainless steel frames also
available.
-
Wide Fin Spacing: Condenser coil(s) are 6 fins
per inch (4.2 mm) heavy gauge hardened aluminum alloy fins 0.0095 (0.251mm)and
copper tubes.
Allows for maintenance-free operation in dirty environments.
-
Independent Condenser Fan Motor: Fan cycling for
low ambient operation is optional on some models.
-
Compressor: Bitzer
octagon semi-hermetic reciprocating compressor. Very low possibility
of leak. Quiet operation. Optional Scroll hermetic compressor for
Severe Duty Design.
-
Refrigerants: Designed for operation with the
following environmentally acceptable refrigerants: HCFC-124,
HFC-134a.
-
Capacity: 18,000 - 60,000 BTUH (5.3kW - 17.6kW).
Capacity can vary depending on refrigerant type, multiple condenser
coils, compressor selection, evaporator selection, blower option and
return air temperature.
-
336 Dimensions: 30.00" [762mm] (W) X
33.50"
[851mm] (L) x 29.00" [736mm] (H).
-
348 Dimensions: 60.00" [1524mm] (w)
x 33.50" [851mm] (L) x 29.00" [736mm] (H).
-
Power Supply: 230/460/3/60 VAC, 380-415/3/50 VAC,
Other voltages available also.

348 Condenser Unit Horizontal
(2) 336 Condenser Units Vertical
|