A one-of-a-kind design, the LHDC36 is designed as a heavy-duty condenser for applications in elevated outside ambient temperature, and exposed to high corrosion and dirty atmospheres found in industrial, marine and tropical environments.
|
| Condenser coil is 8 fins per inch (3.2 mm) compared to 14-22 fins per inch on commercial units. Allows for maintenance-free operation in dirty environments. |
| Type 304 stainless steel frame inside and out with epoxy coated condenser coil as a standard for maximum corrosion protection. |
| Operates up to 135°F (57°C) ambient temperatures. |
| 50°F - 120°F (10°-49°C) Outside air temperature entering condenser for refrigerant HCFC-22. |
| 40.00" [1016mm] (W) X 34.25" [870mm] (H) X 20.00" [508mm] (D). |
| 36,000 BTUH (9,068 kcal/hr) @ 80°F (26°C) return air temperature and outside air-entering temperature @ 95°F (35°C) With refrigerant HFC-134a 60Hz. |
| 30,000 BTUH (7,560 kcal/hr) @ 80°F (26°C) return air temperature and outside air-entering temperature @ 95°F (35°C) With refrigerant HFC-134a 50Hz. |
| 208-230/1/60Hz, 460/3/60Hz, 380/3/50Hz for HFC-134a. |
| Located on the compressor suction line, automatic safety feature turns compressor off with loss of refrigerant charge. |
| Located on the compressor discharge line, automatic safety feature turns compressor off when system pressure exceeds safe operating limits. |
| 1/4" (6.35mm) SAE direct access to the refrigeration circuit discharge and suction lines. This feature allows the service technician to connect a manifold gauge set to the system for future service. Facilitates refrigerant charging. |
|